SAMWONTECH
3rd Edition of TEMI880 IM : Aug. 22. 2005 Page 65 / 123
12
DRY LIMIT
LOW
Set dry limit low.
A case DRY LIMIT LOW of
2.12.1.3 Input Display Screen
is changed, it is changed.
Not modify.
13
TEMP
REFERENCE
POINT1
Set temperature reference point1.
A case DRY LIMIT LOW or HIGH of
2.12.1.3 Input Display Screen
is
changed, it is changed into
(DRY.L + DRY.H) / 2 value.
14
DRY LIMIT
HIGH
Set dry limit high.
A case DRY LIMIT HIGH of
2.12.1.3 Input Display Screen
is changed, it is changed.
Not modify
15
TEMP∙HUMI
PID GROUP
PID group for control temperature
and humidity.
Move PID group setting page.
16
H.CMOD Select control mode at humidity
CMD0 : If you use wide control
object(Ex:Clean Room) selecting DCV
sensor at humidity, you can get a
stable result
CMD1 : If you use narrow control
object(Ex:Chamber) selecting PT or
DCV sensor at humidity, you can get a
stable result.
PID group for control temperature and humidity PID group for control temperature
GROUP 3 GROUP 6
DRY.L TEMP SP T1
H2 < HUMI SP HUMI RH
T1 < TEMP SP < DRY.H
H2 < HUMI SP HUMI RH
GROUP 2 GROUP 5
DRY.L TEMP SP T1
H1 < HUMI SP H2
T1 < TEMP SP < DRY.H
H1 < HUMI SP H2
GROUP 1 GROUP 4
DRY.L TEMP SP T1
HUMI RL < HUMI SP H1
T1 < TEMP SP < DRY.H
HUMI RL < HUMI SP H1
GROUP 9
T3 < TEMP SP TEMP RH
HUMI SP = HUMI RL
GROUP 8
T2 < TEMP SP T3
HUMI SP = HUMI RL
GROUP 7
TEMP RL TEMP SP T2
HUMI SP = HUMI RL
PID Group