Samwon Tech TEMI850 Bedienerhandbuch Seite 71

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 126
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 70
SAMWONTECH
3rd Edition of TEMI880 IM : Aug. 22. 2005 Page 69 / 123
No. Contents Description Additional Description
1
INNER
SIGNAL
Set relay number for the inner
signal output.
See 2.12.3 ON/OFF Signal and Inner
Signal Setting Screen
2
TIME SIGNAL
Set relay number for the time
signal output.
See 2.10.4 Time Signal Setting Screen
3
ALARM
SIGNAL
Set relay number for the alarm
signal output.
See 2.12.6 Alarm and DI Error Name
Setting Screen
4
ON/OFF
SIGNAL
Set relay number for the ON/OFF
signal output.
See 2.12.3 ON/OFF Signal and Inner
Signal Setting Screen
Relay is “ON” after setting time.
Setting time is applied one time.
5
TEMP RUN
SIGNAL
Set relay number for the temperature
running signal output.
It occurs that control temperature at
Fix running or Program running.
Relay is “ON” after setting time.
6
HUMI RUN
SIGNAL
Set relay number for the humidity
running signal output.
It occurs that control humidity at
Fix running or Program running.
Relay is “ON” after setting time.
7
TEMP UP
SIGNAL
Set relay number for the temperature
Up signal output.
9
TEMP DOWN
SIGNAL
Set relay number for the temperature
Down signal output.
FIX RUN
Setting range : EUS 0% ~ EUS 10%
PROG RUN
Relay is “ON” during TSP minus
setting temperature.
Setting range is (EUS 0% ~ EUS 10%)
Status lamp of the running screen and
relay is operated at the same time.
8
TEMP SOAK
SIGNAL
Set relay number for the temperature
Soak signal output.
When Fix running, status lamp of the
running screen is display but relay
output isnt occurred.
When Program running, status lamp
of the running screen and relay is
“ON” during Soak time minus setting
time.
10
HUMI UP
SIGNAL
Set relay number for the humidity
Up signal output.
12
HUMI DOWN
SIGNAL
Set relay number for the humidity
Down signal output.
FIX RUN
Setting range : EUS 0% ~ EUS 10%
PROG RUN
Relay is “ON” during TSP minus
setting humidity.
Setting range is (EUS 0% ~ EUS 10%)
Status lamp of the running screen and
relay is operated at the same time.
Seitenansicht 70
1 2 ... 66 67 68 69 70 71 72 73 74 75 76 ... 125 126