2.10.1 Edit Pattern
Symbol Parameter Setting Range Unit Init. Value
PATTERN NO PATTERN NUMBER 1~120 ABS 1
TEMP SEGMENT TEMP SP T.EU(0~100%) T.EU T.EU(0%)
HUMI SEGMENT HUMI SP H.EU(0~100%) H.EU H.EU(0%)
TIME SEGMENT TIME
-0.01(OFF)~99.59
(HOUR.MIN)
ABS -0.01(OFF)
TS1~TS4 TIME SIGNAL1~4 0~7 ABS 0(OFF)
2.10.2 Set Repeat
Symbol Parameter Setting Range Unit Init. Value
PTN NO PATTERN NUMBER 1~120 ABS 1
PTN RPT
PATTERN REPEAT
COUNT
0(Infinite)~999 ABS 1
LINK PTN LINK PATTERN 0~120 ABS 0
START START SEGMENT 0~99 ABS 0
END END SEGMENT 0~99 ABS 0
COUNT SEGMENT COUNT 0~99 ABS 0
2.10.3 Edit File
Symbol Parameter Setting Range Unit Init. Value
SRC. PTNO
SOURCE PATTERN
NUMBER
1~120 ABS 0
DES. PTNO
DESTINATION
PATTERN NUMBER
1~120 ABS 0
DEL. PTNO
DELETE PATTERN
NUMBER
1~120 ABS 0
2.10.4 Set Time Signal
Symbol Parameter Setting Range Unit Init. Value
ON TIME
TIME SIGNAL
ON TIME
00.00~99.59
(HOUR.MIN)
ABS 00.00
OFF TIME
TIME SIGNAL
OFF TIME
00.00~99.59
(HOUR.MIN)
ABS 00.00
2.10.5 Set Wait Operation
Symbol Parameter Setting Range Unit Init. Value
WAIT MODE WAIT MODE OFF, ON ABS OFF
TEMP ZONE TEMP WAIT ZOME T.EUS(0~100%) T.EUS T.EUS(0%)
HUMI ZONE HUMI WAIT ZOME H.EUS(0~100%) H.EUS H.EUS(0%)
WAIT TIME WAIT TIME
00.00~99.59
(HOUR.MIN)
ABS 0(OFF)